IscAnalysisLF ============== Field Values ------------- .. tabularcolumns:: |\Y{0.15}|\Y{0.25}|\Y{0.6}| .. list-table:: **IscAnalysisLF Field Values** :widths: 2 5 15 :class: tight-table, longtable :header-rows: 1 * - Type - Field Name - Description * - Float - Convergence - Accuracy for load flow solution. * - Integer - MaxIterations - Maximum number of iterations to run the load flow. * - Float - UndervoltagePU - Lower voltage limit for busbars (reporting only). * - Float - OvervoltagePU - Upper voltage limit for busbars (reporting only). * - Integer - LockTaps - Lock all transformer taps based on the following settings: - 0 = Do not lock taps - 1 = Lock taps during outage analysis only - 2 = Lock taps * - Boolean - NoPhaseShift - Do not apply phase shifts to load flow. - False = Use phase shifting in load flow - True = No phase shifting * - Integer - TapOscIterStart - Starts counting the iteration number of transformer tap oscillations. * - Integer - TapOscSuccessive - Number of successive iterations of tap oscillation. * - Integer - TapOscLimit - Tap oscillation limit after which transformer taps are locked. * - Integer - TapOscIterEnd - Stops counting the iteration number of transformer tap oscillations. * - Integer - FillkARatings - Automatically complete kA rating fields for lines. * - Boolean - UseLoadScaling - Enable scaling of loads in the LF calculation. * - Float - RealLoadScale - Per unit factor used to scale all real loads (default = 1.0). * - Float - ReactiveLoadScale - Per unit factor used to scale all reactive loads (default = 1.0). * - Boolean - CheckProtection - Set ``True`` to check protection devices after load flow. * - Boolean - UseLegacyPhiftCheck - Enables or disables the legacy load flow engine code. * - Boolean - DisplayOptionDialog - Setting this field to ``True`` causes the load flow options dialog to be displayed whenever a load flow is required. * - Float - FeederSlackVoltagePU - Sets the busbar voltage for the slack busbar when performing a feeder load flow. * - Integer - FeederSetTarget - Set to 1 to specify a target power when performing a feeder load flow. * - Boolean - SingleTapMovement - Setting this item to ``True`` forces all tap changes to be moved a maximum of one step in each load flow iteration. * - Boolean - SlowTapMovement - Setting this item to ``True`` forces all tap changes to be adjusted every fourth load flow iteration instead of every iteration. * - Integer - WhichImpedance - The default setting is 0 which will use the normal resistance value for branches when performing calculations. Set this value to 1 to use the minimum resistance value for branches when performing calculations. * - Integer - IslandMethod - The default setting is 0 where any island with a slack will have load flow results, assuming the network converges. Setting this value to 1 means any island with a slack busbar must also have a voltage-controlling generator on that busbar in order to have load flow results (again assuming that the network converges). * - Boolean - AutoSelectSlacks - Set ``True`` to automatically select slack busbars in islands where the user has not manually specified a slack busbar. * - Boolean - InitFlatStart - Sets ``True`` to perform flat starts for all load flows until this parameter is reset to ``False``. * - Boolean - FSSetBusbarVoltages - Set ``True`` to reset all busbar voltages during a flat start. * - Boolean - FSIgnoreVoltageControlSettings - Set ``True`` to ignore transformer voltage control settings during a flat start. * - Float - FSVoltageMagnitudePU - Sets the busbar voltage magnitude in per unit during a flat start. * - Float - FSVoltageAngleDeg - Sets the busbar voltage angle in degrees during a flat start. * - Boolean - FSSetTransformerTaps - Set ``True`` to reset the transformer taps during a flat start. * - Boolean - FSIgnoreFixedTaps - Set ``True`` to ignore fixed tap positions during a flat start. * - Integer - FSNominalTaps - Set to 1 to specify that the transformer nominal tap position will be used during a flat start. * - Float - FSTapStartPC - Sets the tap position of transformers in percentage during a flat start. * - Boolean - FSSetInductionMachineSlips - Set ``True`` to force the induction motor slips to a specified value during a flat start. * - Float - FSSlipPC - Sets the induction motor slips in percentage during a flat start. * - Integer - ProfileUse - - 0 = Do not apply load and generator profiles - 1 = Apply load and generator profile category specified by the ``ProfileLoadCategory`` field * - String - ProfileLoadCategory - Pass a string representing the required load/generator profile category name to be used for the next load flow. * - Float - ProfileTimeSliceHrs - Pass a float representing the number of hours in each profile category. * - Boolean - BlockLDCReverse - Set ``True`` to globally block LDC for reverse flowing transformers in the load flow calculation. IscAnalysisLF Class -------------------- .. autoclass:: ipsa.IscAnalysisLF :members: